How Can We Help?
< All Topics
Print

KCN-4ST-* replace the timer operation

Question

Question

I would like to replace the KCN-4ST-* used for timer operation.
Please tell me the successor model and update procedure when updating to the current product.

Answer

Answer

The successor model will be the KT-V series.
Since there are differences in specifications, please check the following notes when replacing.

Replace

Model number comparison table

KCN-S series KT-V series Remarks
KCN-4ST KT-V4S 4-digit AC power supply transistor output
KCN-4ST-C KT-V4S-C 4-digit DC power supply transistor output

Notes

1. The terminal block arrangement and setup menu items / display order are different between KCN-S and KT-V.
2. The key protection method is different.
3. The depth dimension of the product is different. (AC power supply: + 10mm, DC power supply: + 5mm)
4. Set the prediction output setting of KT-V to “zero”.

About operation

Output operation mode Replaceability
Mode A: signal on-delay Available
Mode B: signal off-delay Available
Mode C: one shot Available
Mode D: signal flicker Available
Mode E: integration Available

Input connection method

counter-16-1

Output connection method

counter-17-2

Preset value

KCN-Both S / KT-V are set with each digit key.

Settings in setup mode

The setting order of the setup mode menu is different between KCN-S and KT-V.
In addition, some functions have changed to DIP SW settings.
Please set up referring to the figure below.
– Case of mode D –
counter-16-3
– For modes A / B / C / E –
counter-16-4

Product

Related manual

Related keywords

Inquiry

Table of Contents